ABB ACS800 Series Firmware Manual page 147

Center winder/unwind control program
Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

No.
Name/Value
98.12 AI/O MOTOR TEMP
NAIO
NO
RAIO-SLOT1
RAIO-SLOT2
Description
Activates the communication to the analogue I/O extension module
and reserves the module for the use of the motor temperature
measurement function. The parameter also defines the type and
connection interface of the module.
For more information on the temperature measurement function, see
group
35 MTR TEMP
MEAS.
The use of the analogue inputs (AI) and outputs (AO) of the module is
shown in table below.Before setting the drive parameters, ensure the
module hardware settings are appropriate for the motor temperature
measurement:
1. The module node number is 9.
2. The input signal type selections are the following:
- for one Pt100 sensor measurement, set the range to 0...2 V.
- for two to three Pt100 sensors or one to three PTC sensors, set
the range to 0...10 V.
3. The operation mode selection is unipolar.
Motor 1 Temperature Measurement
AO1
Feeds a constant current to motor 1 temperature sensor.
The current value depends on the setting of
TEMP SEL:
- AO1 is 9.1 mA with selection 1xPT100
- AO1 is 1.6 mA with selection 1..3 PTC
AI1
Measures voltage over motor 1 temperature sensor.
Motor 2 Temperature Measurement
AO2
Feeds a constant current to motor 2 temperature sensor.
The current value depends on the setting of
TEMP SEL:
- AO2 is 9.1 mA with selection 1xPT100,
- AO2 is 1.6 mA with selection 1..3 PTC
AI2
Measures voltage over motor 2 temperature sensor.
Communication active. Module type: NAIO. Connection interface:
Fibre optic DDCS link.
Note: Make the module hardware settings described above. For
instructions, see Installation and Start-up Guide for NTAC-0x/NDIO-
0x/NAIO-0x Modules (Code: 3AFY58919730 [English]).
Inactive.
Communication active. Module type: RAIO. Connection interface:
Option slot 1 of the drive.
Note: Make the module hardware settings described above. The node
number is not required. For directions, see User's Manual for RAIO
Module (Code: 3AFE64484567 [English]).
Communication active. Module type: RAIO. Connection interface:
Option slot 2 of the drive.
Note: Make the module hardware settings described above. The node
number is not required. For directions, see User's Manual for RAIO
Module (Code: 3AFE64484567 [English]).
FbEq
35.01
MTR1
35.04
MTR2
1
2
3
4
Actual signals and parameters
135

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-u2Acs800-u7Acs800-u4

Table of Contents