124
No.
Name/Value
66.07 TORQ MEM SMPL PTR
-255.255.31...+255.255.31
/ C.-32768...C.32767
66.08 TORQ MEM ENBL PTR
-255.255.31...+255.255.31
/ C.-32768...C.32767

67 LEAD CTRL

67.01 WEB SPD INPUT
NOT SEL
AI1
AI2
AI3
AI5
AI6
67.02 WEB SPD SCALE
0...9999.0

70 DDCS CONTROL

70.01 CH0 NODE ADDR
0...254
70.02 CH0 BAUD RATE
8 Mbit/s
4 Mbit/s
2 Mbit/s
1 Mbit/s
70.05 CH2 NODE ADDR
1...125
70.06 CH2 M/F MODE
NOT IN USE
MASTER
FOLLOWER
SPD FOLLOWER
SPDTQ FOLLOW
70.07 MASTER SIGNAL 1
Actual signals and parameters
Description
Defines the source or constant for selection PARAM 66.07 of
66.01
TORQUE MEM SAMPLE.
Parameter index or a constant value. See
information on the difference.
Defines the source or constant for selection PARAM 66.08 of
66.02
TORQUE MEM ENABLE.
Parameter index or a constant value. See
information on the difference.
Winder Lead macro specific parameters.
Note: This group is hidden unless WINDER LD MACRO is selected
Selects the signal source for the web speed feedback.
Not selected.
Analog input AI1 (voltage).
Analog input AI2 (current).
Analog input AI3 (current).
Analog input AI5 (voltage or current).
Analog input AI6 (voltage or current).
Scales the AI maximum (10 VDC / 20 mA) to motor speed at core.
Setting range.
Settings for the fiber optic channels.
Defines the node address for channel 0. No two nodes on-line may
have the same address. The setting needs to be changed when a
master station is connected to channel 0 and it does not automatically
change the address of the slave. Examples of such masters are an
ABB Advant Controller or another drive.
Address.
The communication speed of channel 0.
8 megabits per second.
4 megabits per second.
2 megabits per second.
1 megabits per second.
Defines the node address for channel 2.
Setting range.
Selects how the drive will use CH2 in a Master/Follower ring.
CH2 is not used.
The drive is the master of the ring.
The drive is a follower and receives the data sent from the Master as
defined in the Master's master signal 1, 2, and 3.
See selection FOLLOWER. The speed reference of the drive is
automatically set to follow the master, regardless of the setting in
11.03
EXT1 REF SELECT.
See selection SPD FOLLOWER. The torque reference of the drive is
automatically set to follow the master.
Signal pointer for high speed dataset communications to followers as
command word.
10.05
EXT1 STRT PTR for
10.05
EXT1 STRT PTR for
FbEq
-
-
1
2
3
4
5
6
10 = 1
1 = 1
0
1
2
3
1 = 1
1
2
3
4
5