Line connection and line-side power components
3.10 Combination options, Line Modules with line reactors and line filters
Table 3- 30
Combination options, Basic Line Modules with line filters and line reactors
BLM type
combined
20
40
100
Filter/reactor
kW
kW
kW
BLF
x
x
Remove connection bracket
1)
136
with:
DC link step
up factor or
rectified
FE
value B6
line
reac-
tor
x
1.35
x
x
x
Features that can be achieved
Total cable length for radio interference suppression
according to EN 61800-3
Cat. C2
Cat. C3
shielded
shielded
in m
in m
-
-
-
350
350
630
350
630
Cat. C4
Cat. C4
shielded
unshielded
in m
in m
630
850
1000
1500
630
850
1000
1500
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Can be
operated on
an IT line
system
Yes
Yes
1)
No
No