X1 Line Connection - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.7.2.2

X1 line connection

Table 4- 40
X1: Line supply connection for Basic Line Modules 20 kW
For ring cable lugs without insulation (Page 732)
1)
Table 4- 41
X1: Line supply connection for Basic Line Modules 40 kW
For ring cable lugs without insulation (Page 732)
1)
Note
Compliance with IPXXB degree of protection for Basic Line Modules 40 kW
Degree of protection IPXXB according to EN 60529 for the Basic Line Module 40 kW is only
obtained when power cables with insulated end sleeves and cross-sections > 25 mm
used.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Type: Screw terminal 7 (Page 730)
W1
PE connection
Threaded hole M5 / 3 Nm
Terminal
Technical data
U1
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
V1
Max. connectable cross-section, 50 mm², end sleeves
W1
Tightening torque, min. 6 Nm
PE connection
Threaded hole M6 / 6 Nm
4.7 Basic Line Modules with internal air cooling
1
1)
Line Modules Booksize
are
2
225