Selecting The Dc Link Rectifier Adapter And Dc Link Adapter; Connection Versions For The Dc Link Adapter - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

12.4.4.2

Selecting the DC link rectifier adapter and DC link adapter

Table 12- 2
Overview of the DC link rectifier adapter and DC link adapter
DC link rectifier adapter (cable outlet on top)
6SL3162-2BD00-0AA.
6SL3162-2BM00-0AA.
DC link adapter (cable outlet on side)
6SL3162-2BM01-0AA.
6SL3162-2BM10-0AA.
Note
Using DC link adapters
DC link adapters are only required to configure a multi-tier drive line-up.
12.4.4.3

Connection versions for the DC link adapter

Depending on the technical requirements and the space available in the control cabinet, for
multi-tier drive line-ups, there are different options when it comes to connecting the DC-link
adapter.
Note
Special feature: Short DC-link screws
Because of the compact construction and the required voltage separations, the left-hand DC-
link screws are shorter (16 mm) than the other DC-link screws (20 mm) for modules with 50-
100 mm installation width.
Note
Special feature: Different number of DC-link screws
Modules with an installation width of 200 mm or larger require two screws per DC-link busbar
on the right-hand DC-link connection side in order to carry the higher amperages.
Note
Special feature: Washers during installation of the DC-link adapter
The supplied washers must also be installed on the left-hand side during the installation of
the DC-link adapter for modules with an installation width of 150 mm or greater.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Suitable for module width
50 mm, 100 mm
150 mm, 200 mm, 300 mm
All module widths
50 mm, 100 mm
Cabinet design and EMC Booksize
12.4 Arrangement of components and equipment
Max. connectable cross-
section
10 mm
2
95 mm
2
95 mm
2
95 mm
2
Max. current carrying capaci-
ty
43 A
240 A
240 A
150 A
677