Siemens SINAMICS S120 Manual page 70

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line connection and line-side power components
3.7 Line filters
NOTICE
Damage caused by overheating as a result of an inadmissible mounting position
If the component is not operated in a vertical position with the line supply terminals at the
bottom, then the component can be damaged.
• Only operate the components in a vertical position with the line terminals at the bottom.
Line/load connection
Table 3- 7
Line and load connection, Wideband Line Filter for Active Line Modules
6SL3000-
Rated power [kW]
Line supply connection
L1, L2, L3
Load connection
U, V, W
PE connection
1)
For ring cable lugs without insulation (Page 732)
1)
70
0BE21-6AA.
0BE23-6AA.
16
36
Screw terminals:
Screw terminals
10 mm
3 pole
50 mm
2
M4 / 1.5 ...
M6 / 6 ... 8 Nm
1.8 Nm
Terminal studs
Terminal studs
M5 / 3 Nm
M8 / 13 Nm
0BE25-5AA.
55
, 3 pole
2
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
0BE28-0AA.
0BE31-2AA.
80
120
Screw terminals
Connection lugs
95 mm
, 3-pole
d = 11 mm
2
M8 / 15 ... 20 Nm
M10 / 25 Nm
Comment: No
touch protection
(IP00 acc. to
IEC 60529); touch
protection must be
provided on the
plant/system side.
Terminal studs
M10 / 25 Nm
Booksize Power Units