Siemens SINAMICS S120 Manual page 169

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Internal air cooling
Rated power
Rated short-circuit current
SCCR
3)
Max. total cable length
4)
Cooling method (internal air cooling)
Max. permissible heat sink tempera-
ture
Sound pressure level
Cooling air requirement
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
4)
Table 4- 11
Technical data for Active Line Modules with internal air cooling, part 2
Internal air cooling
Rated power
Infeed
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current:
for AC 400 V
input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 duty (40 %)
for AC 400 V; peak current
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
6SL3130–
7TE21–6AA.
kW
16
kA
65
See Chapter Combination options, Line Modules with line reactors
and line filters (Page 135)
Internal fan
° C
85
dB(A)
< 60
m
/h
56
3
Rated voltage for rated data 3 AC 380 V
kg
7
6SL3130–
7TE28–0AA.
kW
80
kW (P
)
80
n
kW (P
)
106
S6
kW (P
)
131
max
kW
80
kW
131
V
3 AC 380 ... 480 ±10 % (-15 % < 1 min)
ACrms
Hz
47 ... 63
V
24 (20.4 ... 28.8)
DC
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
122
AC
A
128 / 102
AC
A
161
AC
A
200
AC
4.3 Active Line Modules with internal air cooling
7TE23–6AA.
7TE25–5AA.
36
55
65
65
Internal fan
Internal fan
90
83
< 65
< 60
112
160
10
17
7TE31–2AA.
120
120
145
175
120
175
182
192 / 152
220
267
Line Modules Booksize
7TE25–5AA3 +
Active Interface
Module
55
65
Internal fan
83
< 60
160
17
169

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents