Power Loss For Line Filters And Line Reactors - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

DC link components
Braking Module Booksize
Braking Module Booksize Compact
Capacitor Module
Control Supply Module
Line
DC link
12.12.3

Power loss for line filters and line reactors

Table 12- 35 Overview of power loss during rated operation for line filters and line reactors
Basic Line Filters for Active Line Modules
16 kW
36 kW
55 kW
80 kW
120 kW
Basic Line Filter for Active Line Modules with Active Interface Module
16 kW
36 kW
55 kW
80 kW
120 kW
Wideband Line Filter for Active Line Modules
16 kW
36 kW
55 kW
80 kW
120 kW
Basic Line Filter for Smart Line Modules
5 kW
10 kW
16 kW
36 kW
55 kW
Basic Line Filter for Basic Line Modules
20 kW
40 kW
100 kW
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
12.12 Power losses of the components
Unit
W
W
W
W
Unit
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
Cabinet design and EMC Booksize
Power loss
20
< 40
25
70
65
Power loss
16
26
43
56
73
16
26
43
56
73
70
90
110
150
200
5
9
16
26
43
16
26
73
757