12.5 Electrical connection
Danger to life through electric shock if the cutout in the protective cover has been broken
out
Live components are open and accessible if the 24 V terminal adapter or the DC link infeed
adapter are removed. Touching live components can result in death or severe injury.
• Replace the protective cover with the broken out cutouts by a new protective cover.
Note
The 24 V terminal adapter should always be installed to the left of the component located at
the far left, because if it is positioned anywhere else there may not be enough space for the
24 V plug-in jumpers.
If necessary, the 24 V terminal adapter can also be located at the right for 50 mm and
100 mm modules.
12.5.4

Shield connection for terminals X21/X22 on the Motor Module

The diagram below shows a typical shield connection terminal for the shield support of the
cables to terminal X21.
Figure 12-20 Shield connection terminal for the shield support
Danger to life due to electric shock when using screws with the incorrect length
Excessively long screws can come into contact with live parts and can therefore result in
death or serious injury.
• Only use screws with a permissible insertion depth of 4 - 6 mm.
692
WARNING
Shield connection clamp: Weidmüller, type KLBÜ 3-8 SC
WARNING
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8