Siemens SINAMICS S120 Manual page 678

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet design and EMC Booksize
12.4 Arrangement of components and equipment
Table 12- 3
Comparison of the connection versions
Var. Module width
Installa-
[mm]
tion
1
50 ... 100
Right
2
50 ... 100
Right
3
50 ... 100
Left
4
150
Right
5
150 ... 300
Left
6
200 ... 300
Right
Connections as cross-sectional drawings (view from below)
Note
The different connection versions of the DC-link adapter are shown in the following cross-
sectional drawings. Special features are highlighted in bold in the table above.
Variant 1: Module width 50-100 mm, connected to the drive line-up from the right, standard DC-link
busbar
Figure 12-6
678
Current-
DC-link
carrying
adapter
capacity of
6SL3162-...
the
DC-link bus-
bar [A]
≤ 100
2BM01-0AA0 Standard
≤ 150
2BM10-0AA0 Reinforced 2 screws
≤ 100
2BM01-0AA0 Standard
≤ 150
2BM01-0AA0 Standard
≤ 150
2BM01-0AA0 Standard
≤ 200
2BM01-0AA0 Standard
DC-link adapter 6SL3162-2BM01-0AA0 (4 hole)
Standard DC-link busbar (4 mm)
Connecting the DC-link adapter to the module using 2 M4x20 screws
Connecting the DC-link busbar to the module using 2 M4x16 screws
DC-link bridge
Variant 1 (representation from below)
DC-link
Fastening of the
busbar
DC-link adapter
to two DC-link
busbars
2 screws
2 screws
2 screws
2 screws
4 screws
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Screws
Washers
M4x20
No
M4x20
No
M4x16
No
M4x20
No
M4x20
Yes
M4x20
No
Booksize Power Units