Special points to note in relation to mounting on a cold plate
To improve heat transfer, a heat-conducting medium must be used. Special spherical-
indented heat-conducting foil must be used for this purpose. Every Smart Line Module
Booksize Compact is supplied with heat-conducting foil cut to the right size. Note the
mounting position of the heat-conducting foil.
Note
Use heat conducting foil
• Also replace the heat-conducting foil when replacing a component.
• Only use heat-conducting foil released or supplied by Siemens.
Table 5- 6
Heat-conducting foil, 100 mm
5.2.8

Technical data

Table 5- 7
Technical data Smart Line Modules Booksize Compact
Smart Line Module Booksize Compact
Rated power
Infeed
1)
Rated power S1 duty
Infeed power S6 duty (40 %)
Peak infeed power
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current
at AC 400 V
Input current
at AC 380 V / AC 480 V
at AC 400 V; S6 duty (40 %)
at AC 400 V; peak current
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
Heat-conducting foil
6SL3430–
kW
kW (P
)
n
kW (P
)
S6
kW (P
max
kW
kW
V
AC
Hz
V
DC
V
DC
V
DC
V
DC
A
AC
A
AC
A
AC
A
AC
5.2 Smart Line Modules Booksize Compact
Article No.
6SL3162-6FD01-0AA0
6TE21-6AA.
16
16
21
)
35
16
35
3 AC 380 ... 480 ± 10 % (-15 % < 1 min)
47 ... 63
24 (20.4 ... 28.8)
510 ... 720
820 ± 2 %
360 ± 2 %
27.5
29 / 24.5
35
57.5
Line Modules Booksize Compact
343