4. For 100 mm wide components, additionally attach the DC
link busbars using the original M4x16 screws at the left-hand
side of the component.
Finally tighten the screws with 1.8 Nm + 30 %.
Note
To connect the 24 V busbars of the individual components, use the 24 V connectors
provided in the accessories pack.
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
11.3 Reinforced DC link busbars
Result: View of the mounted reinforced DC link busbars with
24 V connectors and 24 V terminal adapter
Accessories