Line Modules Booksize
4.3 Active Line Modules with internal air cooling
Internal air cooling
Rated power
DC link currents
Rated DC link current:
for 600 V:
DC link current:
for 600 V DC; S6 duty (40 %)
for 600 V DC; peak current
Current carrying capacity
DC link busbars
24 V busbars
Electronics current drawn
at 24 V DC
Total power loss
(including electronics losses, see
Power loss tables (Page 756))
DC link capacitance
Active Line Module
Drive line-up, max.
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
3)
Max. total cable length
4)
Cooling method (internal air cooling)
Sound pressure level
Cooling air requirement
Max. permissible heat sink tempera-
ture
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Maximum total cable length = Σ motor cables, line feeder cable from line filter to the Line Module
4)
170
6SL3130–
7TE28–0AA.
kW
80
A
134
DC
A
176
DC
A
218
DC
A
200
DC
A
20
DC
A
1.4
DC
W
1383.6
μF
2820
μF
20000
cos φ
1
See Chapter Overcurrent protection using fuses and circuit breakers
(Page 51)
kA
65
See Chapter Combination options, Line Modules with line reactors
and line filters (Page 135)
Mounted fan
dB(A)
< 73
m
/h
520
3
° C
70
Rated voltage for rated data 3 AC 380 V
kg
23
7TE31–2AA.
120
200
244
292
200
20
1.8
2243.2
3995
20000
1
65
Mounted fan
< 73
520
75
23
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8