Line Modules Booksize
4.9 Smart Line Modules with internal air cooling
4.9.2

Additional safety instructions for Smart Line Modules Booksize

NOTICE
Destruction of the Smart Line Module for an incorrect switch-on or switch-off sequence
It is essential that an appropriate switch-on and switch-of sequence (Page 263) is complied
with in order to control the 5 kW and 10 kW Smart Line Modules; if this sequence is not
observed, the Smart Line Module could be damaged beyond repair.
• Comply with the specified switching sequence.
Note
Connected to the public low-voltage network
Smart Line Modules have been designed for use in the industrial environment and generate
current harmonics on the line side as a result of the rectifier circuit.
When connecting a machine with integrated Smart Line Modules to the public low-voltage
line supply (grid), authorization is required in advance from the local power supply company
(utility company) in the following cases:
• The rated current of the motor ≤ 16 A per conductor.
• The rated motor current does not comply with the requirements specified in EN 61000-3-
2 regarding current harmonics.
262
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8