Siemens SINAMICS S120 Manual page 748

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet design and EMC Booksize
12.11 Notes on electrical cabinet cooling
NOTICE
Damage caused by overheating resulting from covered ventilation slots
Covered ventilation slots can cause the system to overheat.
• Route the connected signal and power cables to the components in such a way that
Note
The distance between the discharge opening of the air condition equipment and the
electronic equipment must be at least 200 mm.
Note
If the components are mounted in a sealed cabinet, an internal air cooling system must be
installed to circulate the air and prevent hot spots. It is best to mount the fan above the
components to optimize the air flow (suction).
Figure 12-43 Examples of cabinet ventilation
748
they do not cover the ventilation slots.
Cooling unit
Control cabinet
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8