Cold plate
Ventilation clearances
above/below
Weight
Default for 400 V line systems; undervoltage trip threshold can be reduced by up to 80 V and is adjusted to the parame-
1)
terized rated voltage
Rated power of a typical standard induction motor at 400 V 3 AC
2)
Note
Disturbance of the 2 x 9 A Double Motor Module with 300% overload during operation on a
16 kW Line Module
The maximum output of a 16 kW Line Module is not sufficient for the operation of a 2 x 9 A
Double Motor Module with 300% overload.
• Do NOT operate a 2 x 9 A Double Motor Module with a 16 kW Line Module with 300%
overload (i.e. only operate a 2 x 9 A Double Motor Module with a 16 kW Line Module, if
the maximum current is limited to 2 x I
• Use at least a 36 kW Active Line Module or Smart Line Module for operation with 300%
overload.
6.4.8.3

Characteristics for Motor Modules Booksize with 300% overload

Rated duty cycles Motor Modules Booksize with 300% overload
Figure 6-81
Figure 6-82
Booksize Power Units
Manual, (GH2), 07/2016, 6SL3097-4AC00-0BP8
6SL3126-
mm
kg
Peak current duty cycle with initial load (300% overload)
Duty cycle with initial load
6.4 Motor Modules with cold plate
2TE13-0AA4
2TE15-0AA4
4.5
).
rated
Motor Modules Booksize
2TE21-0AA4
≥ 80
4.5
4.5