SI motion: Test stop running
NONE
IMMEDIATELY (POWER ON)
The test stop is active.
Message value: (r9749, decimal):
None necessary.
The message is withdrawn when the test stop is completed.
SI motion: Acceptance test mode is active
NONE
IMMEDIATELY (POWER ON)
The acceptance test mode is active. The power on messages of the
safety-relevant motion monitoring functions can be acknowledged
during the acceptance test using the RESET key of the higher-level
control.
None necessary.
The message is withdrawn when exiting the acceptance test mode.
SI MM: STOP A initiated
OFF2
IMMEDIATELY (POWER ON)
The "Safety Integrated" function integrated in the drive on the Motor
Module (MM) has detected a fault and initiated STOP A (pulse
cancellation via the safety shutdown path of the Motor Module).
– Forced checking procedure of the safety shutdown path of the
Motor Module unsuccessful.
– Subsequent response to fault F30611 (defect in a monitoring
channel).
Fault value (r0949, decimal):
0:
Stop request from the Control Unit
Pulses cancelled although SH not selected and there is not
1005:
internal STOP A present.
Pulses enabled although SH is selected or an internal STOP A
1010:
is present.
Subsequent response to fault F30611
9999:
Select safe standstill and then deselect again.
– Replace the Motor Module involved.
Re fault value = 9999:
– Carry-out diagnostics for fault F30611.
10.3 Safety messages for SINAMICS S120