Toshiba Q9+ Installation & Operation Manual page 113

Adjustable speed drives
Table of Contents

Advertisement

V/f 5-Point Setting Voltage 2
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 2 establishes the output voltage
level that is to be associated with the frequency setting of
(V/f 5-Point Setting
Frequency 2).
The
F701
parameter setting will determine if the selection for this
parameter appears in the form of a Voltage (V) or as a Percent-
age (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this parameter.
V/f 5-Point Setting Frequency 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 3 sets the frequency to be
associated with the voltage setting of parameter
Setting Voltage 3).
See
F190
and
F191
for additional information on this parameter.
V/f 5-Point Setting Voltage 3
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Voltage 3 establishes the output voltage
level that is to be associated with the frequency setting of
(V/f 5-Point Setting
Frequency 3).
The
F701
parameter setting will determine if the selection for this
parameter appears in the form of a Voltage (V) or as a Percent-
age (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this parameter.
V/f 5-Point Setting Frequency 4
Program Special V/f 5-Point Setting
The V/f 5-Point Setting Frequency 4 sets the frequency to be
associated with the voltage setting of parameter
Setting Voltage 4).
See
F190
and
F191
for additional information on this parameter.
https://www.toshiba.com/tic/
F193
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F195
F197
F197
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
F192
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
(V/f 5-Point
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
F194
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
(V/f 5-Point
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
F193
F194
F195
F196
101