Toshiba Q9+ Installation & Operation Manual page 84

Adjustable speed drives
Table of Contents

Advertisement

BACnet Setup
Q9 Plus ASD Install/Op Manual
Analog Value
Object Name
Object ID
Analog
VLP
Value #12
Technology
(AV12)
Average
Analog
VLP
Value #13
Technology
(AV13)
Feedback
Analog
VLP
Value #14
Technology
(AV14)
Direct Ref
Analog
VLP
Value #15
Technology
(AV15)
Process Hold
Ref
Analog
Value #16
Freq Ref
(AV16)
Analog
Value #18*
Last Flt
(AV18)
Analog
Value #19*
Prev Flt 1
(AV19)
Analog
Value #20*
Prev Flt 2
(AV20)
Analog
Value #23
Accel Time 1
(AV23)
Analog
Value #24
Decel Time 1
(AV24)
* Refer to the BACnet
®
Option Unit Function Manual for the list of fault codes.
R = Read-only; C = Commandable; W = Writable
72
®
Table 8. BACnet
Analog Values.(Cont)
Description
Average operating Virtual Linear Pump
number
Virtual Linear Pump process feedback
Virtual Linear Pump direct mode com-
mand reference
Virtual Linear Pump process hold
mode command
reference
Frequency reference
Current fault code
Most recent fault code
Second most recent fault code
Changes Acceleration Time 1 (F009)
Changes Deceleration Time 1
Value
-
-
-
-
Hz
-
-
-
Sec
(F010)
Sec
https://www.toshiba.com/tic/
Access
R
R
C
C
C
R
R
R
W
W

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dn-68249-003

Table of Contents