assigned to this terminal). This terminal may be
programmed to provide an output pulse rate that is
proportional to the magnitude of the user-selected
item from
Table 10 on page
information on this terminal see F676.
AM+
AM — The default function assigned to this output
terminal is Output Current. This output terminal
produces an output current or voltage that is
proportional to the magnitude of the Output Current
of the Q9 Plus ASD (or the function assigned to this
terminal). The available assignments for this output
terminal are listed in
further information on this terminal see F670.
FM — This output terminal produces an output
FM+
current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the
function assigned to this terminal. The available
Figure 8. The relay is shown in the normal operating condition (default
setting). During a faulted condition the relay connection is FLC-to-FLA.
Figure 9. Terminal Board.
Terminal Board
1 to 2 = Sys. Supplied (*)
2 to 3 = Ext. Supplied
SW301
S4
(*)
= Default Setting
SW200
SW301
See the section titled
15
for terminal descriptions.
https://www.toshiba.com/tic/
255. For further
Table 10 on page
J100
1 to 2 = Sink (*)
2 to 3 = Source
J101
(24 V)
SW301
V/I Switch ( *I)
TB1
TB2
TB3
TB4
See
Figure 20. on pg. 19
Terminal Descriptions on pg.
Q9 Plus ASD Install/Op Manual
assignments for this output terminal are listed in
Table 10 on page 255.
this terminal see
Current output selection is performed at F681.
FLA — A normally open contact that, under a user-
defined condition, connects to FLC.
FLB — A normally closed contact that, under a
user-defined condition, opens the FLB-to-FLC
connection.
FLC — FLC is the common leg of a single-pole
double-throw form C relay. The FL relay is the Fault
255. For
Relay by default, but may be programmed to any of
the selections of
information on this terminal see F132.
Note:
The FLA, FLB, and FLC contacts are rated
at 2A/120 VAC and 2A/30 VDC.
Ensure that the ground screw is securely in place to
prevent arcing, intermittent operation, or system failure.
SW200
Hal f/F ull D uplex( *) Sw itch
S4
RS485 4-Wire Communication
for more information on the Terminal Board connections.
See the section titled
on pg. 282
terminal sizes and torque specifications when
making Terminal Board connections.
Installation and Connections
For further information on
F005 on pg.
75. The Voltage/
Table 12 on page
257. For further
CAUTION
Cable/Terminal Specifications
for information on the proper cable/
FLC
FLB
FLA
17