My Function Count Data 1
Program My Function My Function Data
This parameter is used to set the pulse-count threshold value
used to trigger the discrete output COUNT1 (ON Timer).
COUNT1 (ON Timer) outputs a 1 upon reaching the threshold
setting of this parameter.
My Function Count Data 2
Program My Function My Function Data
This parameter is used to set the pulse-count threshold value
used to trigger the discrete output COUNT2 (ON Timer).
COUNT2 (ON Timer) outputs a 1 upon reaching the threshold
setting at this parameter.
Input Function Target 1
Program My Function My Function Unit 4
This parameter plays a role in the setup of the My Function fea-
ture by selecting the functionality of the programmable Input
Function Target 1 terminal.
This setting assigns the function of the programmable Input
Function Target 1 terminal to any one of the user-selectable func-
tions listed in
Table 11 on pg.
14 on pg.
260.
See
F977
for additional information on this parameter.
Input Function Command 1
Program My Function My Function Unit 4
This parameter is used to assign a user-selected logical operator
to two user-selected Input Function Target variables, enable a
counter/timer function, or perform a hold/reset function.
Table 15 on pg. 262
lists the available selections. Their use and
selection requirements are described in an example at F977.
236
–
F933
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
256,
Table 12 on pg. 257,
F937
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
or
Table
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 (NOP)
Changeable During Run — Yes
https://www.toshiba.com/tic/
F933
F934
F935
F936