PG Disconnection Detection
Program Feedback PG Settings
This parameter Enables/Disables the system's monitoring of the
PG connection status when using encoders with line driver out-
puts.
Note: The PG Vector Feedback Board option is required to use
this feature.
Settings:
0 — Disabled
1 — Enabled (with Filter)
3 — Enabled (Detect momentary power fail)
Number of RP Terminal Input Pulses
Program Feedback PG Settings
In conjunction with parameter settings F234–F237, this parame-
ter is used to scale the input pulse train speed-control signal
when using the optional Expansion IO Card Option 2.
When using the optional terminal board, the frequency com-
mand can be input via the pulse train input (RP). The input pulse
frequency is calculated to the percent base data which is then
converted to the frequency based on settings F234–F237.
See the Expansion IO Card Option 2 instruction manual
(P/N 58686) for additional information on the function of this ter-
minal.
PID Output Dead Band
Program Feedback PG Settings
While operating in the PID mode, this parameter establishes an
ASD output threshold that must be exceeded in order to activate
the configured PID control.
150
F377
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F380
Direct Access Number —
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number —
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 12
Maximum — 9999
Units — PLS
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %