Over-Torque Detection Level During Regenerative Braking
Program Protection Over-Torque Parameters
This parameter sets the torque threshold level that is used as a
setpoint for over-torque tripping during negative torque (regen).
This setting is a percentage of the maximum rated torque of the
ASD.
This function is enabled at F615.
Over-Torque Detection Time
Program Protection Over-Torque Parameters
This parameter sets the amount of time that the over-torque con-
dition may exceed the tripping threshold level set at
F617
before a trip occurs.
This function is enabled at F615.
Over-Torque Detection Hysteresis
Program Protection Over-Torque Parameters
During a momentary over-torque condition, this parameter pro-
vides a torque threshold level to which the over-torque condition
must return within the time setting of
will be incurred.
Cooling Fan Control
Program Protection Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
Cumulative Operation Time Alarm Setting
Program Protection Special Protection Parameters
This parameter sets a run-time value that, once exceeded, closes
a discrete output contact. The output signal may be used to con-
trol external equipment or used to engage a brake.
Associate the Total-Operation-Hours Alarm setting of
page 257
to a discrete output contactor.
Note: The time displayed is 1/10th of the actual time (0.1 hr. = 1.0
hr.).
https://www.toshiba.com/tic/
F617
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F618
or an Over-Torque Trip
F622
Direct Access Number —
Parameter Type — Numerical
Factory Default — 250.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.50
Changeable During Run — Yes
F616
and
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — 10.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Direct Access Number —
Parameter Type — Selection List
Factory Default — Automatic
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 610.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 999.9
Table 12 on
Units — Hours (X 10)
F617
F618
F619
F620
F621
187