PG Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the speed of the PG input termi-
nals when the PG terminal is used as the control input.
This parameter sets PG Point 1 Frequency and is the frequency
that is associated with the setting of PG Point 1 Setting.
See PG Point 1 Setting (F234) for additional information on this
parameter.
PG Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction and speed of the PG
input terminals when the PG terminals are used as the control
input.
This parameter sets the PG input signal that is associated with
PG Point 2 Frequency.
This value is entered as 0% to 100% of the PG input signal
range.
See PG Point 1 Setting (F234) for additional information on this
parameter.
PG Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction and speed of the PG
input terminals when the PG terminals are used as the control
input.
This parameter sets PG Point 2 Frequency and is the frequency
that is associated with the setting of PG Point 2 Setting.
See PG Point 1 Setting (F234) for additional information on this
parameter.
122
–
F235
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F240
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
https://www.toshiba.com/tic/
F235
F236
F237