RX Input Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input
terminal when the RX terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets RX Input Point 1 Frequency and is the fre-
quency that is associated with the setting of RX Input Point 1 Set-
ting when operating in the Speed Control mode.
See RX Input Point 1 Setting (F216) for additional information on
this parameter.
RX Input Point 2 Setting
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input
terminal when the RX terminal is used as the control input while
operating in the Speed Control mode or the Torque Control
mode.
This parameter sets the RX input level that is associated with RX
Input Point 2 Frequency when operating in the Speed control
mode or is associated with the RX Input Point 2 Rate when oper-
ating in the Torque Control mode.
This value is entered as -100% to +100% of the RX input signal
range.
See RX Input Point 1 Setting (F216) for additional information on
this parameter when used for Speed control.
See RX Input Point 1 Rate (F220) for additional information on
this parameter when used for Torque Control.
RX Input Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RX input
terminal when the RX terminal is used as the control input while
operating in the Speed Control mode.
This parameter sets RX Input Point 2 Frequency and is the fre-
quency that is associated with the setting of RX Input Point 2 Set-
ting when operating in the Speed Control mode.
See RX Input Point 1 Setting (F216) for additional information on
this parameter.
114
F217
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F220
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — +100
Changeable During Run — Yes
Minimum — -100
Maximum — +100
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq.
(F011)
Units — Hz