Command Mode
Program Fundamental Standard Mode Selection
The Command Mode Selection establishes the source of the
command input for the ASD. Command inputs include Run, Stop,
Forward, etc. The Override feature may supersede the Com-
mand Mode Selection setting (see
quency Mode Control on pg.
Settings:
0 — Terminal Board
2 — EOI Keypad
3 — RS485/BACnet
4 — Communication Option Board
Frequency Mode 1
Program Fundamental Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the fre-
quency-control input for the ASD. The Frequency Mode 2 setting
or the Override feature may supersede the Frequency Mode 1
setting.
Note: Only Bolded items from the Settings list below may be
placed in the Override Mode. See the section titled
Command Mode and Frequency Mode Control on pg. 33
additional information on the Override feature.
Settings:
1 — V/I
2 — RR
3 — RX
5 — EOI Keypad
6 — RS485/BACnet
7 — Communication Option Board
8 — RX2 (AI1 Option)
9 — Option V/I (AI2 Option)
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
74
–
F003
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Command Mode and Fre-
33).
F005
Direct Access Number —
Parameter Type — Selection List
Factory Default — Terminal
Board
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — RR
Changeable During Run — No