Toshiba Q9+ Installation & Operation Manual page 160

Adjustable speed drives
Table of Contents

Advertisement

Process Lower Limit
Program Feedback Feedback Settings
Selecting Process PID at parameter
ter setting to function as the Lower Limit while operating in the
PID Control mode.
PID Control Delay Time
Program Feedback Feedback Settings
This parameter is used to delay the start of PID control at start
up. During the wait time set here, the ASD will follow the fre-
quency control input of the process value and the feedback input
will be ignored. When this setting times out, the PID setup
assumes control.
PID Output Upper Limit
Program Feedback Feedback Settings
Selecting Speed PID at parameter
ter setting to function as the Upper Limit while operating in the
PID Control mode.
PID Output Lower Limit
Program Feedback Feedback Settings
Selecting Speed PID at parameter
ter setting to function as the Lower Limit while operating in the
PID Control mode.
148
F368
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F359
allows for this parame-
F359
allows for this parame-
F359
allows for this parame-
F372
Direct Access Number —
Parameter Type — Numerical
Factory Default — Lower-Limit
Freq.
(F013)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 2400
Units — Seconds
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
Direct Access Number —
Parameter Type — Numerical
Factory Default — Lower-Limit
Freq.
(F013)
Changeable During Run — Yes
Minimum — Lower-Limit Freq.
(F013)
Maximum — Upper-Limit Freq.
(F012)
Units — Hz
https://www.toshiba.com/tic/
F368
F369
F370
F371