Virtual Linear Pump Command Value
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation while
operating in the Process Hold mode and using the EOI for sys-
tem control, this parameter establishes the Virtual Linear Pump
level.
This parameter setting is effective ONLY while operating in the
Process Hold mode and while receiving a command via the EOI.
The end value of this parameter setting appears in the Fre-
quency Command screen as shown below.
Virtual Linear Pump Low Frequency Limit
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the Virtual Linear Pump Low Frequency
Limit.
Autotune 1
Program Motor Vector Motor Model
This parameter sets the Autotune command status.
Selecting Reset Motor Defaults for this parameter sets parame-
ters F410, F411, F412, and
If selecting Autotune on Run Command, Autotune Initiated by
Input Terminal, or Autotune of Detail Parameters for this parame-
ter set the Base Frequency, Base Frequency Voltage, and the
Motor Rated Revolutions to the nameplated values of the motor
to achieve the best possible Autotune precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see
page
252)
4 — Motor Constant Auto Calculation
156
F397
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F413
to the factory default settings.
Table 9 on
F401
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum —
Direct Access Number —
Parameter Type — Numerical
Factory Default — 15.00
Changeable During Run — Yes
Minimum — 1.00
Maximum — 60.00
Units — Hz
Direct Access Number —
Parameter Type — Selection List
Factory Default — Autotune Dis-
abled
Changeable During Run — No