Motor Constant 3 (Leak Inductance)
Program Motor Vector Motor Model
This parameter is used to set the leakage inductance of the
motor.
A larger setting here results in higher output torque at high
speeds.
Motor Constant 4 (Rated Slip)
Program Motor Vector Motor Model
This parameter is used to set the secondary resistance of the
motor.
An increase in this parameter setting results in an increase of
compensation for motor slip.
Exciting Strengthening Coefficient
Program Special Special Parameters
This parameter is used to increase the magnetic flux of the motor
at low-speed. This feature is useful when increased torque at low
speeds is required.
Stall Prevention Factor 1
Program Protection Stall
This parameter is to be adjusted in the event that the motor stalls
when operated above the base frequency.
If a momentary heavy load occurs the motor may stall before the
load current reaches the stall prevention level setting of F601.
A drop in the supply voltage may cause fluctuations of the load
current or may cause motor vibration. A gradual adjustment of
this parameter may alleviate this condition.
Start with a setting of 85 at these parameters and gradually
adjust them from there one at a time until the desired results are
produced.
Adjustments to this parameter may increase the load current of
the motor and subsequently warrant an adjustment at the Motor
Overload Protection Level setting.
160
–
F412
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F417
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 0
Maximum — 250
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — (ASD-Depen-
dent)
Changeable During Run — No
Minimum — 0.10
Minimum — 25.00
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 100
Maximum — 130
Units — %
Direct Access Number —
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 10
Maximum — 250
https://www.toshiba.com/tic/
F412
F413
F415
F416