Virtual Linear Pump Mode Switch
Program Virtual Linear Pump Settings
This parameter is enabled for use by completing the Virtual Lin-
ear Pump Setup Wizard.
During a properly configured Virtual Linear Pump operation, this
parameter establishes if feedback is used or not.
Select the command source or the feedback source for operat-
ing in the Direct or Process modes, respectively, at F396. The
default selection for each may be used.
Note: If
F396
is set to use V/I as the command source, DO NOT
set this parameter to Process Hold. Doing so will result in
an error message (V/I cannot be used for both functions).
Note: The selected setting for this parameter will be retained
when the Virtual Linear Pump function is turned on or off
using a discrete input terminal set to Virtual Linear Pump
Enable/Disable.
Settings:
0 — Disabled
1 — Direct Mode (No Feedback Used)
2 — Process Hold (V/I Feedback Used)
255 — Setup
(Virtual Linear Pump) Application Type
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the process variable measurement type.
Settings:
0 — Pressure
1 — Flow
2 — Level
(Virtual Linear Pump) Transducer Output Range
Program Virtual Linear Pump Settings
During a properly configured Virtual Linear Pump operation, this
parameter establishes the transducer output signal type and
range for Virtual Linear Pump operation.
Note: This parameter is scaled at
and requires no user intervention.
Settings:
0 — 0 – 20 mA
1 — 4 – 20 mA
2 — 0 – 10 V
3 — 0 – 5 V
154
F390
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F201
F204
for either selection
F393
Direct Access Number —
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — Pressure
Changeable During Run — No
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 – 20 mA
Changeable During Run — No