MON2 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON2
analog output terminal. The available assignments for this output
terminal are listed in
Table 10 on page
The MON2 analog output terminal produces an output voltage or
current that is proportional to the magnitude of the function
assigned to this terminal.
Note: The Expansion IO Card Option 2 option board (P/N
ETB004Z) is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N
58686) for additional information on the function of this terminal.
MON2 Terminal Setup Parameters
F674
— MON2 Output Function
F675
— MON2 Terminal Meter Adjustment
F691
— MON2 Voltage/Current Output Switching
F692
— MON2 Output Gradient Characteristic
F693
— MON2 Bias Adjustment Set Zero Level
MON2 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON2 output termi-
nal and is used in conjunction with the settings of parameter
F674.
See
F674
for additional information on this parameter.
Pulse Output Function
Program Terminal Analog Output Terminals
This parameter sets the functionality of the FP output terminal to
any one of the user-selectable functions listed in
page
255.
As the assigned function changes in magnitude or frequency, the
pulse count of the FP output terminal pulse train changes in
direct proportion to changes in the assigned function.
Note: The duty cycle of the output pulse train remains at
65 ±5.0 µS.
This parameter is used in conjunction with F677.
200
F674
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
255.
Table 10 on
F677
Direct Access Number —
Parameter Type — Selection List
Factory Default — Output Fre-
quency
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 682
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number —
Parameter Type — Selection List
Factory Default — Output Fre-
quency
Changeable During Run — Yes
https://www.toshiba.com/tic/
F674
F675
F676