Combined Terminal Function (cont.)
8.Enable the My Function parameter at
Function Always On.
With the aforementioned setup completed in the example, once
the Low-Speed Signal AND the Low Current Alarm are active,
the OUT1 terminal is activated for the duration of the Low-Speed/
Low Current condition.
See the My Function Instruction Manual (P/N E6581335) for a
complete description of the setup requirements and operational
information of the My Function parameter.
https://www.toshiba.com/tic/
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F977
by selecting My
F977
Direct Access Number —
Parameter Type — Selection List
Factory Default — None (Dis-
abled)
Changeable During Run — No
DANGER
This parameter must always be
set to None at the start of the My
Function setup and remain set to
None until all of the My Function
parameter settings have been con-
firmed as being correct.
If enabled for normal operation
using settings 1 or 2, the motor
may start and engage the driven
equipment unexpectedly upon
receiving a Run signal during the
My Function setup.