Toshiba Q9+ Installation & Operation Manual page 238

Adjustable speed drives
Table of Contents

Advertisement

Communication 2 Time-Out Condition
Program Communications Communication Options
This parameter determines the condition under which the drive
will detect time-out errors.
Settings:
0 — Always Detect
1 — Detect Time-Out Error During Communications
2 — Detect Time-Out Error During Communications and
Running
Disconnection Detection Extended Time
Program Communications Communication Options
This parameter is used to set the length of time that no communi-
cations activity may exist before the communications link is dis-
connected.
ASD Operation at Disconnect
Program Communications Communication Options
This parameter is used to set the Q9 Plus ASD action to be car-
ried out in the event of the loss of communications.
Settings:
0 — Stop and Terminate Communication
1 — Do Nothing (Continue Programmed Operation)
2 — Deceleration Stop
3 — Coast Stop
4 — Emergency Off
5 — Preset Speed (Setting of F852)
Preset Speed Operation
Program Communications Communication Options
This parameter setting is used to set the Preset Speed selection
to be used if Preset Speed is selected at parameter F851.
Settings:
0 — Disabled
1–15 — Preset Speed Number
226
F849
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F853
Direct Access Number —
Parameter Type — Selection List
Factory Default — Always Detect
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — Seconds
Direct Access Number —
Parameter Type — Selection List
Factory Default — Stop and Ter-
minate Communication
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
https://www.toshiba.com/tic/
F849
F850
F851
F852

Advertisement