Parity (2-Wire RS485)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications
network by establishing the Parity setting of the communications
link.
The communications network includes other ASDs and Host/
Control computers that monitor the status of the ASD(s), trans-
fers commands, and loads or modifies the parameter settings of
the ASD.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
ASD Number
Program Communications Communication Settings
This parameter plays a role in the setup of the communications
network by assigning an identification (ID) number to each ASD
in the communications network.
The communications network includes other ASDs and Host/
Control computers that monitor the status of the ASD(s), trans-
fers commands, and loads or modifies the parameter settings of
the ASD.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
Communications Time-Out (2- and 4-wire RS485)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications
network by setting the time that no activity may exist over the
communications link before the link is severed (Time Out).
The communications network includes other ASDs and Host/
Control computers that monitor the status of the ASD(s), trans-
fers commands, and loads or modifies the parameter settings of
the ASD.
Changes made to this parameter require that the power be
cycled (off then on) for the changes to take effect.
https://www.toshiba.com/tic/
–
F801
Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
F804
Direct Access Number —
Parameter Type — Selection List
Factory Default — Even Parity
Changeable During Run — Yes
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 247
Direct Access Number —
Parameter Type — Numerical
Factory Default — 0 (Off)
Changeable During Run — Yes
Minimum — 0 (Off)
Maximum — 100
Units — Seconds
F801
F802
F803
213