NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
System
Optional
Parts
Issue 09 (2022-12-15)
Parameter
Networking
mode
Number of
systems in this
group
Number of
running systems
in this group
Return air sensor
Cold aisle sensor
Hot aisle sensor
Cold aisle
temperature and
humidity sharing
Hot aisle
temperature and
humidity sharing
Motorized
damper
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
Description
Specifies the networking mode for
teamwork control. The networking mode
selected on the screen must match the
actual networking mode. Otherwise, the
teamwork function is unavailable.
Specifies the total number of units in this
group. The value is an integer ranging from
1 to 32.
NOTE
This parameter is displayed after Teamwork
function is set to Enable.
Specifies the number of running units in this
group. The value is an integer ranging from
1 to the value of Number of systems in
this group.
NOTE
This parameter is displayed after Teamwork
function is set to Enable.
Enables or disables a sensor.
Enables or disables a sensor.
Enables or disables a sensor.
This function can be enabled only when at
least one smart cooling product in the
teamwork group is equipped with cold aisle
T/H sensors. If this function is enabled, the
master unit in the teamwork group collects
the cold aisle temperature and humidity
values from all units equipped with cold
aisle sensors, and synchronizes the
temperature and humidity control type and
setpoints to all slave units.
This function can be enabled only when at
least one smart cooling product in the
group is equipped with hot aisle T/H
sensors. If this function is enabled, the
master unit in the teamwork group collects
the hot aisle temperature and humidity
values from all units equipped with hot aisle
sensors, and synchronizes the temperature
and humidity control type and setpoints to
all slave units.
● Disable: The air damper function of the
unit is disabled.
● AO Ctrl: Select AO Ctrl for AO-type air
dampers.