NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 6-7 Cable connections
Step 8 Reinstall the fan by performing
Step 9 Turn on the general switch and fan switch QF4. The display module lights up.
Choose Alarms > Query Act. Alarms and tap Indoor fan 2 communication
failure (used as an example) to access the Details screen.
● If two or more fans need to be replaced onsite, replace the first fan and clear
its alarm. After replacing the first fan, power off the smart cooling product.
Then replace the next fan and clear its alarm.
● Ensure that the indoor fan communication failure alarm to be cleared
corresponds to the fan that is being processed.
Step 10 Tap Repair in the lower left corner. The Connect the cable to the
communications port on the fan to be repaired and disconnect the cables
from the communications ports on other faulty fans. message is displayed.
Then tap Yes. The command is triggered successfully and the alarm is cleared.
Step 11 Power on the device, tap Start on the home screen, choose Maintenance >
Startup Wizard, and commission the indoor fan to check that it works properly
before you exit.
Step 12 Install the fan maintenance baffle and close the front door.
Step 13 On the home screen, choose Maintenance > Performance Maintenance to enter
the Performance Maintenance screen and clear the runtime of the indoor fan.
----End
Issue 09 (2022-12-15)
NO TE
The preceding figure shows fan 2.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Step 7
to
Step 2
and connect the cable.
6 Maintenance