How Do I Handle Active Alarms - Huawei NetCol8000-C070 User Manual

Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Procedure
Step 1 Tap the
----End

7.4.9 How Do I Handle Active Alarms?

Procedure
Step 1 Tap
screen to enter the active alarms screen.
Step 2 You can tap an alarm to go to the Details screen of the alarm. The alarm details
include the alarm name, generation time, severity, location, cause ID, code,
possible cause, and handling procedure.
Figure 7-14 Alarm details
● If the
cleared. Such an alarm can be automatically cleared after the fault is rectified.
● If the
cleared manually. You need to tap Clear to clear the alarm after the fault is rectified. The
alarm clearance type (automatic or manual) varies with smart cooling products. Some of the
alarms can either be cleared automatically or manually. Perform operations as required.
Step 3 Tap Fault Diagnosis_Repair to view the diagnosis report. Rectify the faults
following instructions in the diagnosis report.
Issue 09 (2022-12-15)
icon in the status bar, tap Off. The icon changes to
NO TE
● Active alarms are displayed by generation time. The latest generated alarm is displayed
in the uppermost row.
● If active alarms exist, they are displayed on the alarm bar in turn.
● You can query an alarm on the alarm list in "Alarm Reference" based on the alarm ID to
know causes of the alarm and methods to clear the alarm.
NO TE
icon is not displayed on the Details screen, the alarm can be automatically
icon is displayed on the Details screen, it indicates that the alarm can be
Copyright © Huawei Digital Power Technologies Co., Ltd.
(or choose Alarms > Query Act Alarms) on the home
7 FAQ
.
182