NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 4-6 Access Control
Parameter
Remote control
SSH (LAN)
4.5.4.2 Setting Communications Parameters (RTU Protocol)
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > Modbus Settings.
Figure 4-7 Modbus Settings
Step 2 Set the baud rate, communication address, and RS485 monitoring group. For
details, see
Issue 09 (2022-12-15)
Description
● Enable: Users can control the unit over their
● Disable: Users cannot control the unit over their
● Enable: Access to the unit through the intranet using
● Disable: Access to the unit through the intranet
● If this parameter is set to Disable, the function will
● If this parameter is set to Enable, the function will
Table
4-8.
Copyright © Huawei Digital Power Technologies Co., Ltd.
monitoring system.
monitoring system.
SSH (default port number: 22) is allowed.
using SSH is not allowed.
be enabled within 30 minutes after power-on by
default.
be automatically disabled after 24 hours of running.
4 Power-On Commissioning
117