3.2.2.4 Pipe Support

Figure 3-9
Figure 3-9 Pipe support (unit: mm)

3.2.2.5 Cables

● The onsite grounding resistance must comply with related standards.
● Select power cables with appropriate diameters based on the maximum
working currents.
When connecting cables, fit them with protective hoses.
Issue 09 (2022-12-15)
NO TE
(1) in the dotted box is a reserved port. Other items need to be purchased.
shows a pipe support. The supports used onsite may vary.
NO TE
● The height of a U-shaped pipe clamp equals the diameter of the pipe with thermal
insulation foam minus 5 mm. The pipe supports are to be purchased.
● Stainless steel 304 is recommended for pipe supports and pipe clamps.
● Install a support every 2500 mm in the straight sections of pipes, and 1000 mm away
from each bending point in the turning section.