Figure 4-12 Setting the SNMP port
Step 6 Tap Next Page.
Step 7 Set SNMP trap parameters.
1.
2.
3.
4.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the USB port of the main control
board and successfully identified, tap Export File under MIB File to export the
MIB file to the USB flash drive for the customer's use in accessing a third-party
NMS.
Before using a USB flash drive, ensure that its data has been scanned by antivirus
software and is secure.

4.5.5 (Optional) Setting WIFI Parameters

Prerequisites
After connecting the WIFI module of the USB interface to the USB port of the
smart cooling product main control module, WIFI Settings is enabled to be set.
Issue 09 (2022-12-15)
NO TE
SNMP Port is set to 161 by default.
Tap Add under SNMP Trap.
Set Trap Address as planned and Trap Port to the actual port number.
NO TE
Trap Port is set to null by default.
Select SNMP Version. If an SNMPv3 user is configured, it is recommended
that SNMP Version be set to SNMPv3.
If SNMP Version is set to SNMPv3, you need to select SNMPv3 User Name.
For other protocols, you need to set Trap Community.