● Connect pipes and then wrap thermal insulation foam around the whole
pipeline.
● Based on the hardening property of yellow adhesive, inject water and preserve
the pressure at least 8 hours after an adapter is connected.
Step 2 To avoid deforming the pipe, use a 75# open-end wrench to hold the pipe nut, use
a 36# open-end wrench to hold the plug, and then remove the plug, as shown by
(2) in
Step 3 Apply thread sealant evenly on the joints of external screw threads, and install the
pipes from inside out, as shown by (3) in
Step 4 Use a 75# open-end wrench and 18# pipe wrench to fix the pipe, as shown by (4)
in
Figure
Step 5 Install the pipe baffle plate at the bottom of the cabinet, and wrap the pipe with
thermal insulation foam, as shown by (5) in
Figure 3-24 Connecting pipes
----End
3.5.3 (Optional) Installing Pipes for the External Water Valve
Actuator
Ensure that the arrow direction on the water valve actuator is consistent with the
water flow direction.