NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Menu
Issue 09 (2022-12-15)
Parameter
DO_2
Floor water
overflow alarm
action
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
Description
● If this parameter is set to Smoke &
Water only, DO_2 acts according to
DO_2 action when a smoke or water
overflow alarm is generated.
● If this parameter is set to Critical alarm,
DO_2 acts according to DO_2 action
when a critical alarm is generated.
● If this parameter is set to Major alarm,
DO_2 acts according to DO_2 action
when a major alarm is generated.
● If this parameter is set to Alarm, DO_2
acts according to DO_2 action when a
critical alarm, major alarm, or warning is
generated.
● If this parameter is set to Startup status,
DO_2 acts according to DO_2 action
when the unit is started.
● If this parameter is set to Power
abnormal, DO_2 acts according to DO_2
action when a power exception alarm is
generated.
● If this parameter is set to No, no alarm is
generated when DO_2 is disconnected.
Set the action of the device if there is water
overflow on the floor based on the actual
scenario.
● Shutdown: The device shuts down when
a floor water overflow alarm is
generated.
● Inactivity: The device runs as usual when
a floor water overflow alarm is
generated.
● Only indoor fan running: Only the indoor
fan runs when a floor water overflow
alarm is generated.
● Humidifier stopped: Only the humidifier
is stopped when a floor water overflow
alarm is generated.