4.9 (Optional) Antifreezing

Context
If the NetCol8000-C will be idle for a long time, ensure that the circulation water
inside the system has a temperature no lower than 3°C, and two methods are
used for antifreezing.
This section uses method 2 as an example.
Procedure
Step 1 Remove the plugs from the drainage needle valves of the heat exchanger.
Issue 09 (2022-12-15)
Method 1: Fill glycol into the system to prevent the heat exchanging pipes of
the smart cooling product from freezing up and cracking at low temperatures
scenarios.
Method 2: Use the drainage method to drain all water out of the NetCol8000-
C, and to prevent the heat exchanger from cracking.
(For the upflow units) Remove the plugs from the drainage needle valves 1
and 2 of the heat exchanger, to drain water naturally until no water flows out.
Figure 4-24 The drainage needle valves of the heat exchanger (upflow)
(1) Drainage needle valve 1
(For the downflow units) Remove the plugs from the drainage needle valves
1, 2, 3, and 4 of the heat exchanger, to drain water naturally until no water
flows out.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
(2) Drainage needle valve 2
131