4.5.1 Setting T/H Sensor Parameters

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > System Settings > T/H sensor. The screen
shown in
Figure 4-3 T/H Sensor
Step 2 Set Return air sensor 2 to Enable.
Step 3 Set the temperature and humidity parameters by referring to
Table 4-4 Parameter description
Parameter
Temperature and
humidity control type
Temperature control
mode
Humidity alarm mode
Issue 09 (2022-12-15)
If T/H sensors outside cabinets have been deployed in the aisle, enable the
sensors. Otherwise, skip
If you need to enable a humidity and temperature sensor, log in as the admin
user.
This section describes how to enable Return air sensor 2.
Figure 4-3
is displayed.
NO TE
You are not recommended to modify the parameters not listed in
Copyright © Huawei Digital Power Technologies Co., Ltd.
Step
2.
Description
When the application scenario is non-aisle
containment, you are advised to choose Return air.
Choose Cold aisle if cold aisle T/H sensors are
installed. Hot aisle is not recommended.
The temperature inside the equipment room or aisle is
controlled based on the average value, maximum
value, or minimum value collected by multiple sensors.
Set this parameter as required.
4 Power-On Commissioning
Table
4-4.
Table
4-4.