Huawei NetCol8000-C070 User Manual page 47

Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
To ensure the optimal operating condition and longest service life, install the
equipment correctly as required.
Precautions
Layout Requirements
Issue 09 (2022-12-15)
Install the equipment according to the design drawing and reserve space for
maintenance.
The NetCol8000-C downflow unit that supports only bottom pipe routing
must be installed in an equipment room with a raised floor.
The NetCol8000-C upflow unit that supports side pipe routing can be placed
on the concrete floor of the equipment room or secured using a base.
The NetCol8000-C upflow unit that supports bottom pipe routing can be
secured only using a base.
Thermal insulation measures should be applied to outdoor water pipes to
prevent drainage blockage or insufficient water supply due to freezing.
The equipment top should be sealed during installation (before power-on)
with baffle plates or plastic bags to prevent dust from accumulated on the
top of the equipment or entering the equipment.
Check whether the environment meets the requirements before installation,
and whether reconstruction is required for routing water pipes and cables and
constructing ventilation pipes.
Ensure that the equipment room provides good heat insulation, and that the
walls and floor are dampproof.
To ensure good ventilation, do not place the equipment in the corner of a
room or at the end of a long and narrow room.
During system operation, all doors and windows of the equipment room
should be closed to reduce the additional load of the smart cooling product.
Install the equipment in a spacious place.
The equipment should be placed as far away from offices as possible, and
noise control measures should be taken.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190

Table of Contents