Installing Components; Checking The Nitrogen Pressure - Huawei NetCol8000-C070 User Manual

Hide thumbs Also See for NetCol8000-C070:
Table of Contents

Advertisement

NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Step 3 Check the type and quantity of fittings against the packing list. If some fittings are
missing or do not comply with the models in the packing list, record the
information and contact the supplier immediately.
----End

3.4 Installing Components

3.4.1 Checking the Nitrogen Pressure

Context
The device has been injected with 0.2–0.6 MPa Nitrogen before delivery. Check the
nitrogen pressure for nitrogen leaks.
Procedure
Step 1 Open the front door.
Step 2 Check whether the bonnet of the drainage valve inside the cabinet is missing.
Issue 09 (2022-12-15)
If it is missing, contact technical support.
NO TICE
– In scenarios of multiple modules, you can perform such operations on any
exhaust valve or drainage valve.
– You can open or close the exhaust valve using a flat-head screwdriver.
If no, rotate the exhaust valve counterclockwise. If gas flows out, the system
is normal. If no gas flows out, contact technical support.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c130Netcol8000-c190

Table of Contents