NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
Figure 3-5 Space requirements for downflow units (installed side by side)
(A) Bottom pipe routing

3.1.4 System Requirements

If the water inlet temperature exceeds 10°C or the total load is less than 30% of
the cooling capacity of a single smart cooling product, the humidity may be high.
The customer is advised to add a dehumidifier (engineering procurement).
Issue 09 (2022-12-15)
NO TE
● The height of the raised floor for downflow units must be greater than 550 mm. (The
550 mm space under the floor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
● L indicates the front maintenance clearance, and the minimum value is 900 mm. If this
requirement cannot be met, the minimum clearance after the front door is removed can
be 800 mm.
NO TE
● The height of the raised floor for downflow units must be greater than 550 mm. (The
550 mm space under the floor is used only for fan rotation. The fan rotation area
cannot be occupied by pipes or cables.) Properly determine the positions for routing
pipes and cables to avoid interference.
● L indicates the front maintenance clearance, and the minimum value is 900 mm. If this
requirement cannot be met, the minimum clearance after the front door is removed can
be 800 mm.
● This installation mode is not recommended for upflow units.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
(1) NetCol8000-C
3 Installation
39