Siemens SINAMICS S120 Function Manual page 182

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Basic functions
6.2 Reference parameters/normalizations
Scaling for servo object
Table 6-2
Scaling for servo object
Size
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference angle
Reference acceleration
Reference frequency
Reference modulation depth
Reference flux
Reference temperature
Reference electrical angle
Scaling for object A_Inf
Table 6-3
Scaling for object A_Inf
Size
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation depth
Reference temperature
Reference electrical angle
Scaling for object B_Inf
Table 6-4
Scaling for object B_Inf
Size
Reference frequency
Reference voltage
Reference current
Reference power
182
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = p2003
100 % = r2004
100% = p2005
100% = p2007
100 % = p2000/60
100 % = Maximum output
voltage without overload
100 % = Rated motor flux
100% = 100°C
100 % = 90°
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = r2004
100 % = Maximum output
voltage without overload
100% = 100°C
100 % = 90°
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = r2004
Default at initial commissioning
Induction motor p2000 = Maximum motor speed (p0322)
Synchronous motor p2000 = Rated motor speed (p0311)
p2001 = 1000 V
p2002 = Motor limit current (p0338); when p0338 = "0", 2
* rated motor current (p0305)
p2003 = p0338 * p0334; when "0", 2 * rated motor torque
(p0333)
r2004 = p2003 * p2000 * π / 30
90°
0.01 1/s
2
-
-
-
-
-
Default at initial commissioning
p2000 = p0211
p2001 = r0206/r0207
p2002 = p0207
r2004 = p0206
-
-
-
Default at initial commissioning
P2000 = 50
p2001 = r0206/r0207
p2002 = p0207
r2004 = p0206
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4