Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Bit
Meaning
3
Fault active
4
Coasting active (OFF2)
5
Fast stop active (OFF3)
6
Power-on disable
7
Alarm present
8
Speed
setpoint-actual value deviation
within tolerance band
9
Control requested
10
f or n comparison value reached or
exceeded
Note:
The message is parameterized as follows:
p2141 Threshold value
p2142 Hysteresis
11
I, M or P limit reached or exceeded
366
Comments
1
Fault active
The drive is faulty and, therefore, out of service.
The drive switches to power-on inhibit once the
fault has been acknowledged and the cause has
been remedied.
The active faults are stored in the fault buffer.
0
No fault present
No active fault in the fault buffer.
1
No OFF2 active
0
Coasting active (OFF2)
An OFF2 command is present.
1
No OFF3 active
0
Fast stop active (OFF3)
An OFF3 command is present.
1
Power-on disable
A restart is only possible by means of OFF1 and
then ON.
0
No power-up inhibit
Power-up is possible.
1
Alarm present
The drive is operational again. No
acknowledgement necessary.
The active alarms are stored in the alarm buffer.
0
No alarm present
No active alarm in the alarm buffer.
1
Setpoint-actual value monitoring within tolerance
band
Actual value within a tolerance band; dynamic
overshoot or shortfall permitted for t < t
permissible, e.g.
n = n
±
setp
f = f
±, and,
setp
t
can be parameterized
max
0
Setpoint/actual value monitoring not within
tolerance band
1
Control required
The PLC is requested to assume control. Condition
for applications with isochronous mode: drive
synchronized with PLC system.
0
Local operation
Control only possible on device
1
f or n comparison value reached or exceeded.
0
f or n comparison value not reached.
1
I, M or P limit not reached
0
I, M or P limit reached or exceeded
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
BICO
BO: r2193.3
BO: r0899.4
BO: r0899.5
BO: r0899.6
BO: r2139.7
BO: r2197.7
max
BO: r0899.9
BO: r2199.1
BO: r1407.7
(inverted)