12.8.2

Replacing a device

Order number SINAMICS Sensor Module Integrated:
– SMI10: 6SL3055-0AA00-5NA0
– SMI20: 6SL3055-0AA00-5MA0
In the case of spare part installation, transfer the data previously saved on the
CompactFlash card to the new Sensor Module.
Data transfer from CompactFlash card to Sensor Module
1. Enter the component number of the new Sensor Module (p0141) in p4690.
2. Activate the data backup via p4691 = 2.
3. Execute POWER ON for all DRIVE-CLiQ components.
4. Backup the data of all SINAMICS Sensor Modules Integrated with p4692 = 1.
NOTICE
Only consistent compliance with the procedures and with their systematic, complete
documentation in the LOGBOOK enables a reproduction of all service steps, extensions or
alterations to the drive system.
Supplementary conditions
● The Sensor Module files are stored in a block structure. These blocks are placed directly
● The Sensor Module must be empty before the exchange.
Overview of key parameters (see SINAMICS S List Manual)
● p4690 SMI component number
● p4691 Backup SMI data
● p4692 Backup all SMI data
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
next to each other (internal data of the SINAMICS Sensor Module Integrated | encoder
block | motor block). If a Sensor Module already contains an encoder block and motor
block, and these stored blocks are smaller than the blocks that are to be backed up, then
the backup is rejected.
Backup is also rejected when only one of the two files is stored on the Sensor Module.
Basic information about the drive system
12.8 Exchanging a SINAMICS Sensor Module Integrated
503